6-UNIT Digital Meters

back

6-UNIT Digital Meters

4-digit, Input Loop Powered, Field Indicators

  • 70 mm dia. , D 21 mm (6DV, 6DVI)
  • W 110 x H 118 x D 92 mm (6DV-B, 6DVI-B)
  • 4-digit red LED (-1999 to 9999)
  • 4-20 mA input powered
  • No external power source required
  • Scaling & linearization selectable via the front control buttons
  • Mountable on top of head-mount transmitter, installed together in an outdoor encloure (6DV, 6DVI)
  • NEMA 4X, IP66 / IP67 (6DV-B, 6DVI-B)
CE ATEX FM Intrinsically Safe IP66/IP67

Depending on the model.

Number of Display Digits 4 Digits No External Power Source Needed
  • Two-wire Loop Powered LED Indicator with Intrinsically safe approval

    Model 6DV is a 4-digit, 8-mm-high (.3”), 7-segment red LED display, which is powered from a two-wire current loop (4 to 20 mA), requiring no extra power source. The maximum voltage drop caused by inserting the 6DV into the loop is 4.0 V at 20 mA.

    · The display range is programmable from -1999 to 9999 and the decimal point is also selectable (10–1, 10–2, 10–3 or without decimals).

    · Programmable functions include input signal calibration, offset setting and linearization (SQRT, RT32 and RT52, and 21-point user’s table).

    · In combination with Model 27HU, it provides the user with a low-cost, field-mounted HART Temperature Transmitter with LED Display.

    · Compact housing: External dimensions of 70mm-dia. (2.76”) and 21mm-high (.83”) (See below Figure 1).

    External view and dimensions of 6DV, 6DVI
    Figure 1. External view and dimensions of 6DV, 6DVI

    Using the A-34 DIN Rail Adaptor or the A-6 Spacer, various mounting styles are available.

  • Intrinsically safe approvals are available from ATEX Directive (Europe) and FM (US, Canada). Differences between the 6DV and the 6DVI exist only in safety parameters (See Table 1).

    A safety barrier with matching safety parameters to the 6DV or 6DVI must be installed for complete intrinsic safety. The safety barrier should meet the Ex-data of this unit and must be approved for hazardous location.

    Table 1

    Operating Temperature
      Temp Class Operating Temperature
    6DV 6DVI
    FM/ATEX T4 Intrinsically safe T4 -40 to +80°C -40 to +85°C
    T5 -40 to +60°C -40 to +60°C
    Intrinsic Safety Ex Data
      6DV 6DVI
    Ui (Vmax) 30V DC 28V DC
    Ii (Imax) 100mA DC 120mA DC*1
    Pi (Pmax) 0.75W 0.84W
    Ci 1.0 nF 1.0 nF
    Li 0 mH 0 mH

    *1. Max. current allowed for the safety approval; Not to guarantee the product’s performance.

  • Model 6DV and 6DVI are approved to applicable standard of IEC60079 category: ia, and can be installed into hazardous areas Zone 0 (Europe) and Division 1 (US, Canada). They are covered for use in a potentially explosive atmosphere of the gas group (explosion group) including Hydrogen and Acetylene (See Table 2).

    The 6DV and 6DVI Series also include an optional outdoor enclosure, Model 6DV-B and 6DVI-B, which are able to be field-mounted.

    Table 2

    Safety Approval
    FM: Intrinsically safe Class I, Div. 1, Groups A, B, C and D
    Class I, Zone 0, AEx ia IIC (US)
    Class I, Zone 0, Ex ia IIC (Canada)
    T4 and T5
    (Class 3600)
    (Class 3610)
    (ANSI/ISA 60079-0)
    (ANSI/ISA 60079-11)
    (CAN/CSA-C22.2 E60079-0)
    (CAN/CSA-C22.2 E60079-11)
    TIIS: Intrinsic safety (6DV) Ex ia IIC T5
    ATEX: Intrinsic safety EX II 1G, Ex ia IIC; T4, T5, Ga
    (EN 60079-0)
    (EN 60079-11)