Web Browser Views

Web Browsed Views Designed for Mobiles

· iPhone and iPad are registered trademarks of Apple Inc.
· Android and Android logo are trademarks of Google Inc.
· The screen is an image only.
· Mobile terminals (smartphones, tablets) or mobile network operator services are not our products.

PC Screen
PC Screen
Smart Phone Screen
Smart Phone Screen
Large sized buttons are placed for ease of operating on the small sized screen of a smart phone.

Short trend and digital data displays are available to monitor analog, discrete and totalized pulse signals. Event log is also available to review alarm events. All the views can be quickly ready for use by simple setting.

Trend

Trend
Trend View Specifications
Sampling rate 1 s / 5 s / 10 s / 30 s / 1 min / 5 min / 10 min / 30 min / 1 h / 1 day
Number of pages 8 pages
Number of chs 4 chs per page
Pen color User defined (RGB)
Graph range User defined (engineering unit value)
Number of samples Max. 7200 points per ch
Scrollable charts 1 to 10 (720 samples @chart span)

Event Log

Event Log
Event Log Specifications
Analog signal Alarm triggered when measured value passes across the setpoint.
Discrete signal Alarm triggered when status changes.
Totalized count Alarm triggered when pulse count exceeds the setpoint. (Counter can be reset.)
Pulse signal Alarm triggered when measured value passes across the setpoint.

E-mails can be sent when an event occurs.
Specific recipients and texts can be defined for each event condition.

Data

  • Analog Input Data Display
    Analog Input Data Display
  • Discrete Input Data Display
    Discrete Input Data Display
  • Pulse Input Data Display
    Pulse Input Data Display
  • Discrete Output Data Display
    Discrete Output Data Display
  • Analog Output Data Display
    Analog Output Data Display

Customized Web Browser Views (DL8-D,E Option)

DATA View BY HTML  Example using the DL8 original tags
GRAPHIC View  Example using JavaScript
Using the DL8 Original Tags
Using the DL8 Original Tags

The DL8 original tags in an HTML file are automatically converted into corresponding text/data string by the DL8.
Users who do not have technical knowledge of programming scripts can easily create an original data view.

The DL8 User Defined View must be created and used under the user’s sole responsibility, including its Display components and functions.

Original Tag Contents Converted Text/Data String (example)
[NAME1] Name 1 Web Data Logger
[NAME2] Name 2 Web Data Logger
[NAME3] Name 3 Web Data Logger
[TIME1] Present Time 2012/02/29 11:00:00
[TIME2] Not Used ----
[AI1_NAME] Ai1 CH name
[AI1_COMM] Ai1 CH comment
[AI1_DATA] Ai1 Engineering unit data
[AI1_DATA_P] Ai1 % data
[AI1_UNIT] Ai1 Engineering unit
[AI1_AREA] Ai1 Zone name
[DI1_NAME]
  ·
  ·
  ·
[DO1_DATA]
Di1
  ·
  ·
  ·
Do1
CH name
  ·
  ·
  ·
Status (display comment)
[AO1_NAME] Ao1 CH name
[AO1_COMM] Ao1 CH comment
[AO1_DATA] Ao1 Engineering unit data
Creating User's Original Views by JavaScript or HTML

Measured data strings can be output as JavaScript arrays. Users who have knowledge and skills of JavaScript language, HTML and CSS used to build a web site can freely create original trend graphs, bargraphs and graphic views. Analog input, analog output, discrete input, discrete output, trend data, event data and other variety of array files are available.

Turning Pump ON/OFF
Setting Valve Opening

· Simulated Imagery. View samples are not provided by us.

JavaScript Array Files
JavaScript Array Files