| Figure 1. MDCAT External Appearance and Dimensions |
Power-over-Ethernet compatible
- 1000BASE-T / 100BASE-TX / 10BASE-T
- Ideal to protect network devices powered from Ethernet such as webcams
- Conforms to IEC 61643-21, Categories C1, C2
M-System’s model MDCAT is specifically designed to protect communication devices connected via Ethernet LAN from lightning surge entering through network cables.
1000BASE-T and PoE
Multi-stage protection is provided for all four pairs of conductors in Cat. 5e performance (1000BASE-T, 100BASE-TX and 10BASE-T) with minimal interference, tested for up to the maximum 100 meter segment length as defined in the standard. An equal level of protection is ensured for the core-to-core voltage used for PoE.
Both Alternative A and Alternative B configurations are usable to supply power to the protected network device.
 |
| Figure 2. MDCAT application examples. |
Installation Options and DIN Rail Grounding
Compact module can be placed close to PCs, wireless hubs/switches and webcams in rolled-up LAN cables. It can also be snapped on a DIN rail for high-density mounting in a 19-inch rack together with Ethernet switches or inside a control panel with PLCs. Individual earth wiring is not necessary when you ground the DIN rail.
 |
|
 |
Figure 3. Clustered
mounting on a DIN rail. |
|
Figure 4. DIN rail grounding & shortcircuit bar. |
Shield/Grounding Options
Shield terminal, frame grounding, signal grounding may be provided or not depending on the protected devices. The MDCAT is provided as ‘grounding’ mode with a shortcircuit bar connecting the shield and the ground terminals. Removing the bar turns the module to ‘floating’ mode, so that a ground loop problem can be easily fixed. By separating the shield and the ground, the former terminal can be used for individual signal grounding.
| Table1. Performance |
| |
LINE-LINE
per signal pair |
LINE-LINE
PoE |
LINE-EARTH |
Max. continuous
operating voltage Uc |
±6 V |
±58 V |
±150 V |
Voltage protection
level Up |
±15 V max.
@2 kV |
±100 V max.
@2 kV |
±600 V max.
@4 kV |
| Leakage current @Uc |
25 µA |
25 µA |
5 µA |
| Response time |
4 nsec. max. |
4 nsec. max. |
20 nsec. max. |
Max. discharge current
Imax |
100 A |
100 A |
10 kA |
| Nominal current IN |
1 A |
| Series resistance |
Approx. 0 Ω |
|
Every year lightning destroys millions of dollars of sensitive electronic equipment. Millions more are lost through extended down time and loss of production or mission-critical information.
That’s why companies around the world depend on on-line M-Rester Lightning Surge Protectors. The M-Rester absorbs only the lightning surges with no interruption of instrumentation signal.
| Product Bulletins |
A4:  |