Four poles of terminals are equipped on each of surge side and protected side, three for signal and one for shield. By adapting an independent set of shield terminals, floating and grounding can be selected in free combinations to suit users applications. HIGH PERFORMANCE
The maximum discharge current capacity is as high as 20 kA for an impulse wave of 8/20 microseconds. The MD7 Series are tested according to IEC 61643-21 standard to be suitable for categories C1, C2 and D1. C1 category requires the surge protector to withstand 300 times of average induced surges, C2 to withstand 10 times of strong induced surges generated in a harsh environment without electromagnetic shielding. D1 category is tested by two direct hits. EASY COMMISSIONING When the DIN rail is grounded at single point, surge protectors mounted on it are automatically connected to the earth. There is no need of cross-wiring individual module. Thanks to the terminal blocks slightly slanted forward, access from the front side to the terminals is easy even after the protectors are mounted on the rail. INDEPENDENT SHIELD TERMINAL In the floating mode, the shield is normally insulated from the signal and the ground by a discharge element. When an elevated potential is detected by a lightning surge, the discharge element is immediately activated to prevent discharge at an undesirable location. In the grounding mode, the shield is normally connected via the signal line with a low potential difference of several to several tens of volts, and connected permanently to the ground. Each installation or network protocol requires different earth grounding method,
such like both-end grounding, single-end grounding, SG terminal connection (Figure
1). The MD7 Series provide the most suitable grounding type for each application.
(Table 1)
LOOP DISCONNECT FUSE The model MD7ST, designed specifically for 4-20 mA loop, is provided with fuses to disconnect a failed device from the power bus supplying multiple devices. When the device protected by the MD7ST fails in shortcircuit mode, the fuse separates it from the power bus and protects the entire system. M-Systems surge protectors are designed and identified for specific sensors or devices. Not only the selection of discharge elements but also the disposition of discharge elements and wiring routes are carefully studied for the most effective protection for each sensor/device type. Needless to say, it is easy to choose for you. There is no need of finding/knowing appropriate protection level values. Presently available product line-up is indicated in Table 2. More varieties for three-wire transmitters, strain gauge, pulse generating sensors will be added in the future.
|
|||||||||||||||||||||||||||||||||||||||||||
| |
|||||||||||||||||||||||||||||||||||||||||||
| Copyright (C)2006 M-System Co., Ltd. All rights reserved. |